Subject: Re: [sloan-25mlog 3842] 2.5m obslog 20180117 (SJD 58136) From: John Downey Date: Thu, 18 Jan 2018 06:15:21 -0700 >=20 > Note to engineers and developers: > =3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D= =3D=3D=3D=3D=3D=3D=3D=3D=3D > 1. axis init cleared all axes. But alt came on after 10' motion. Inter = locked > showed that wind-alt was red although the knife switch was turned on = and green > light was on. Anyway, tagging the knife switch fixed the problem. The ALT windbaffle amp is more susceptible to getting stuck in an error = state than are the other amps - the most common cause I've seen is = stopping the WB suddenly. The telescope will usually clear all axes and move in ALT until it hits = the windbaffle in this case. I don't think it used to clear the axis in = such cases, but I didn't work with the old ALT windbaffle drive long = enough to be certain of this - I just never saw the telescope drive into = the windbaffle and then stop until we installed the new system. Power cycling the WB drive clears the error condition if it was = temporary - such as caused by a sudden stop - so that was what I would = have recommended.=